Overview

The FS20X is a Multi-Spectrum and UV/Dual IR/VIS Flame Detector with a proven UV solar-blind sensor. The FS20X exhibits faster false-alarm free response to fire over a wider temperature range and with a much longer detection range compared to conventional UV/IR detectors. It has detection range in excess of 200 feet (very high sensitivity setting) for the detection of a one square-foot Heptane reference fire and has a cone of vision greater in volumetric coverage than most UV/IR detectors.

Features
- Patented WideBand IR™ Infrared combined with Ultraviolet
- Detection range greater than 200 feet to 1 sq. ft. heptane fire
- Patented Electronic Frequency Analysis
- Visible Sensor for optimum false alarm rejection
- Selectable detection sensitivities
- Solar blind 90° full 100% cone-of-vision
- Dual Microprocessors for reliable performance
- Real-time clock for accurate time dating of events
- FirePic™ — Up to 6 pre-fire event data storage
- Event log — Up to 200 events with date and time stamp
- Built-in RS-485 ModBus Communication
- Alarm, Fault and Fire Verification relays
- Automatic Optical Path and Electronic Self-Test
- Widest operating temperature range

Major Applications
- Refineries and oil production facilities
- Off-Shore platforms
- Turbine/Compressor enclosures
- Acetylene processing and storage
- Oil and Gas pipelines and pumping stations
- LNG/LPG loading and unloading facilities
- Natural Gas and CNG plants
- Ethanol, Methanol, and IPA production
and storage
- Crude oil and gasoline storage and tank farms
- Aircraft hangars
- Hydrogen plants and storage
- Paint and solvent storage
- Chemical production, storage, and loading facilities
- Power plants
- Silane gas storage

Technical Specifications
- FIELD OF VIEW 90° Horizontal Cone of vision, ± 45° from on axis
- SENSITIVITY Very high (60m), high (45m), medium (30m) and low (15m) - switch selectable
- RESPONSE TIME : 3-5 Seconds to 0.1 m2 (1 sq. ft.) n-Heptane fire at 30 m (100 ft.); 3-10 Seconds to 0.1 m2 (1 sq. ft.) n-Heptane fire at 60 m (200 ft.)
- SPECTRAL SENSITIVITY : Ultraviolet: 185 - 260 nanometres, Visible: 400 – 700 nanometres, Near Band IR: 0.7 – 1.1 microns, Wide Band IR: 1.1 – 3.5 microns
- OPERATING VOLTAGE : 24 Vdc nominal (18-32 Vdc) - regulated
- POWER CONSUMPTION : Operating: 85 mA @ 24 Vdc nominal

General Specifications
- TEMPERATURE RANGE : Operating: -40 to +85ºC (-40 to +185ºF), Storage: -55 to +110ºC (-67 to +230ºF)
- HUMIDITY RANGE : 5 to 98% relative humidity, non-condensing
- VIBRATION : Meets or exceeds MilSpec 810C Method 514.2, Curve AW12
- WIRING : 2.5 mm2 (14 AWG) to 0.326 mm2 (22 AWG); shielded cable recommended
- CONDUIT ENTRIES Standard: Two M25 or two ¾” NPT
- ENCLOSURE MATERIALS : Copper-free powder coated aluminum or 316 stainless steel
- ENCLOSURE TYPE 4X, IP66 and NEMA 4
- CERTIFICATIONS : FM: Class I, Div. 1 & 2, Groups B, C, & D; Class II, Div. 1 & 2, Groups E, F, & G;Class III , ATEX/IECEx: II 2 G Ex db IIC T4 (Ta: -40 to +110°C), T5 (Ta: -40 to +75°C), T6 (Ta: -60 to +60°C), II 2 D Ex tb IIIC T135°C, II 2 G Ex db IIC T4 (Ta: -60 to +110°C), CE :- Complies with EN6100-6-4 & EN50130-4